Role Of Air Gaps On Ac Withstand Voltage Of An Ice-Covered Insulator String

IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION(2006)

引用 34|浏览11
暂无评分
摘要
The influence of the number and position of air gaps on the 50% ac withstand voltage, V-50, of a short string of 5 IEEE standard insulator units covered with ice was experimentally investigated and numerically simulated. The results show that the V-50 is affected by the number and position of the air gaps. The results also show that the presence of a partial are along the air gap close to the high voltage (HV) electrode leads to a redistribution of the voltage along the ice-covered insulator. Based on the obtained results, suggestions for improving the performance of line insulators under icing conditions were proposed.
更多
查看译文
关键词
ice-covered insulator, voltage distribution, finite element method, air gap, modeling and simulation, withstand voltage