Novel adaptive algorithm for optimal relay setting with improved coordination

Engineering and Systems(2014)

引用 1|浏览1
暂无评分
摘要
With the penetration of distributed generation (DGs) at distribution level, protection of a distribution network is quite challenging due to the change in operating mode and system topology. Thus the relay settings have to be updated every time there is a change in network configuration. This paper presents a novel adaptive algorithm with fastest backup protection in which new optimal relay settings (pickup current and time dial setting) calculated by proposed algorithm solves the problem regarding changing of coordination time interval and critical clearing time as mode changed. This proposed algorithm uses the numerical inverse overcurrent relays which have the capability of memory storage and to cope up with communication. The proposed algorithm has been verified on test systems of different operating modes using MATLAB/Simulink and C program. Results showed the importance and necessity of this scheme in maintaining the optimal performance of the relays under changing operating modes.
更多
查看译文
关键词
distributed power generation,power distribution protection,relay protection,c program,matlab,simulink,adaptive algorithm,coordination time interval,critical clearing time,distributed generation,distribution network protection,fastest backup protection,memory storage capability,numerical inverse overcurrent relays,optimal relay,adaptive protection,co-ordination time interval (cti),distributed generation (dg),overcurrent relay (ocr),time dial setting (tds),optimization
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要