An Experimental Study on Evaluation of Bond Strength of Arc Thermal Metal Spaying According to Treatment Method of Water Facilities Concrete Surface

Journal of the Korean Institute of Building Construction(2016)

引用 3|浏览0
暂无评分
摘要
In this study, the bond strength of metal spraying system by surface treatment of concrete (waterproof/corrosion method) in water treatment facilities was evaluated. The results showed that the system with Sa-P-R-(S) (sanding-perviousness surface hardener-surface roughness agent-metal spraying-sealing) led to the desirable performance. The bond strength, the coefficient of water permeability and air permeability were 3.7MPa, 0.68*10 -8 cm/sec, and 0.45*10 -16 ㎠, respectively. In scanning electron microscope analysis, the microstructure of specimen coated with perviousness surface hardener was much denser than that without it. Therefore, the specimen coated with sanding-perviousness surface hardener-surface roughness agent-metal spraying-sealing had the best bond performance and was the most suitable system to concrete surface in water treatment facilities.
更多
查看译文
关键词
arc thermal metal spaying,bond strength,concrete
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper