Assessment Of Absolute Partial Discharge Intensity From A Free-Space Radiometric Measurement

2016 URSI ASIA-PACIFIC RADIO SCIENCE CONFERENCE (URSI AP-RASC)(2016)

引用 9|浏览4
暂无评分
摘要
Partial discharge (PD) is measured simultaneously using free-space radiometric (FSR) and a galvanic contact measurement technique based on the IEC 60270 standard. The PD source is an emulator of the floating-electrode type. The radiated signal is captured using a biconical antenna. A method of estimating absolute partial discharge (PD) activity level from a radiometric measurement by relating effective radiated power to PD intensity using a PD calibration device is presented.
更多
查看译文
关键词
Partial discharge,free space radiometric measurement,galvanic contact measurement,PD calibration