Precise Locating Method of Generator Stator Grounding Fault Point Based on Injected Signal

Han Hangjie,Gao Jun, Zhao Huimian,Li Li,Yu Kun,Zeng XiangJun

international conference on advanced power system automation and protection(2019)

引用 0|浏览5
暂无评分
摘要
In view of the difficulty and low accuracy of stator grounding fault location for large generators, a method for accurate stator grounding fault location based on neutral injection signal is presented in this paper. Inject Non-power-frequency current signal into the stator neutral point during shutdown. The branch current is measured at the head and end of the fault phase branch. The fault branch is detected by the current difference comparison method at the head and end of the branch. The coil measurement point in the sub-fault branch is set by the dichotomy method to accurately locate the fault point to the slot number. The principle of adjusting current limiting resistance to improve detection accuracy is analyzed. The method can significantly improve the accuracy of stator grounding fault location. This way can reduce the downtime and effectively increase the efficiency of stator grounding fault treatment.
更多
查看译文
关键词
Current amplitude,Capacitance Current Loss,Grounding fault,Injection signal,Locating fault points