谷歌浏览器插件
订阅小程序
在清言上使用

Single-ended protection principle of LCC-VSC three-terminal DC system based on Gini impurity

CSEE Journal of Power and Energy Systems(2021)

引用 0|浏览5
暂无评分
摘要
Due to the advantages of LCC-VSC (line-commutated converter-voltage source converter) three-terminal DC technology in terms of new energy consumption, long-distance transmission, reliability and economy, China has successively constructed a number of hybrid DC transmission projects. However, there is very little research on the protection principle of this topology. And it has problems such as different control strategies, different line boundary elements, and different operating time requirements. A technology based on the Gini impurity of the line mode voltage is proposed as the main protection scheme. This protection principle uses Gini impurity to describe the degree of confusion of fault information caused by boundary elements and further identifies internal and external faults. Finally, different faults are set to verify the reliability and superiority of the proposed protection scheme. A large number of results show that the protection scheme based on Gini impurity can identify the fault type within 1ms under the interference of 600Ω resistance and 10dB noise.
更多
查看译文
关键词
LCC-VSC technology,Line main protection,Gini Impurity,Intrinsic mode singular value