This brief aims to perform security threat assessment of networked control systems with regulatory and supervisory control layers. We analyze the performance of a proportional-integral controller (regulatory layer) and a model-based diagnostic scheme (supervisory layer) under a class of deception attacks. We adopt a conservative approach by assuming that the attacker has knowledge of: 1) the system dynamics; 2) the parameters of the diagnostic scheme; and 3) the sensor-control signals. The deception attack presented here can enable remote water pilfering from automated canal systems. We also report a field-operational test attack on the Gignac canal system located in Southern France.
更多
查看译文
关键词
Delay systems,fault diagnosis,intrusion detection,supervisory control and data acquisition (SCADA) systems,supervisory control