This paper provides insight into a failure mechanism that impacts a broad range of industrial equipment. Voltage surges have often been blamed for unexplained equipment failure in the field. Extensive voltage monitoring data suggests that voltage sags occur much more frequently than voltage surges, and that current surges that accompany voltage sag recovery may be the actual culprit causing equipment damage. A serious limitation in equipment specification, is highlighted, pointing to what is possibly the root-cause for a large percentage of unexplained equipment field failures. This paper also outlines the need for a standard governing the behavior of equipment under voltage sags, and suggests solutions to protect existing equipment in the field.
更多
查看译文
关键词
voltage sags,current surges,equipment failure,process control,converter control,utility interface