Pcb, Pcdf, And Pcdd Exposure Following A Transformer Fire - Chicago

CHEMOSPHERE(1986)

引用 11|浏览5
暂无评分
摘要
On September 28, 1983, an electrical fire in a transformer vault resulted in the loss of 15 gallons of transformer oil composed of 65% PCBs (Aroclor 1260) and 35% trichlorobenzene and forced the precautionary evacuation of a major Chicago office building. A square foot wipe sample of soot on the vault ceiling contained 28,000 ng total TCDFs, 3,800 ng 2,3,7,8-TCDF, 40,000 ng PCDFs, 33,000 ng HxCDFs, 11,200 ng HpCDFs, 1,238 ng OCDFs, 314 ng HpCDDs, and 127 ng OCDDs. No PCDFs or PCDDs were detected in the blood (detection limit 3–40 ppt) of two fire fighters hospitalized with smoke inhalation nor of two office employees similarly exposed.