Robust control design of multiple resonant controllers for sinusoidal tracking and harmonic rejection in Uninterruptible Power Supplies

Industrial Electronics(2010)

引用 24|浏览4
暂无评分
摘要
This paper presents a robust control strategy for tracking sinusoidal reference signals with zero steady state error and harmonic compensation in Uninterruptible Power Supplies - UPS. Multiple resonant controllers are derived for DC-AC inverters when supplying energy to (uncertain) nonlinear loads to obtain a nice tradeoff between transient response and disturbance rejection regardless possible load variations. The controller parameters are determined by means of a convex optimization problem subject to a set of linear matrix inequalities (LMIs). Real time experiments demonstrate the potentials of the proposed approach for controlling UPS systems.
更多
查看译文
关键词
dc-ac power convertors,control system synthesis,convex programming,harmonics suppression,linear matrix inequalities,resonant power convertors,robust control,transient response,uninterruptible power supplies,dc-ac inverters,lmi,ups systems,convex optimization problem,disturbance rejection,harmonic compensation,harmonic rejection,load variations,multiple resonant controllers,robust control design,sinusoidal reference signal tracking,zero steady state error,linear matrix inequality,real time,resonant frequency,harmonic analysis,frequency control,steady state,convex optimization