PML Assisted Power System Parameter Calibration at Jiangsu Electric Power Company

2017 IEEE POWER & ENERGY SOCIETY GENERAL MEETING(2017)

引用 0|浏览8
暂无评分
摘要
An online PMU-assisted Power System Parameter Calibration System (PSPCS) was recently developed and implemented at State Grid Jiangsu Electric Power Company (JEPC). PSPCS leverages high-resolution PMU data and data mining techniques to perform online screening of the EMS and Production Management System (PMS) databases for data cleaning, model validation, and parameter calibration. PSPCS calculates transmission line and generator parameters on a regular real-time basis and compares the results with databases to identify record(s) with significant discrepancy, if any. Once consistent discrepancy is observed, the system will raise a flag and further investigation will be initiated, including a novel density-based spatial clustering procedure for parameter/data calibration. A novel metric is proposed to quantify the credibility of PMU-based parameter identification. This paper discusses the proposed methodologies, challenges, as well as implementation issues identified during the development and deployment of PSPCS.
更多
查看译文
关键词
Phasor Measurement Unit, data calibration, transmission line parameter, generator parameter, credibility metric
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要