Triggering Bess Inertial Response With Synchronous Machine Measurements

2018 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM)(2018)

引用 2|浏览11
暂无评分
摘要
Synthetic inertia devices must deliver power during maximum RoCoF, which is observed to occur during the first 500 ms post fault. The use of a droop characteristic with a deadband is demonstrated to be unfit for purpose. The ideal response (with present technologies) is demonstrated to be a maximum power ramp in minimum time post fault. This paper demonstrates a method of rapidly detecting and categorizing under frequency events by monitoring synchronous machines. PMU and point on wave data, sampled at 6.4 kHz, from a power station and a laboratory set up, under transient events, is presented. A rapid inertial power ramp signals the onset of the events. Sub-cycle voltage and current variations are demonstrated as a potential method for reliably detecting frequency transients and triggering a synthetic inertia response.
更多
查看译文
关键词
droop characteristic,deadband,maximum power ramp,minimum time post fault,frequency events,wave data,power station,transient events,rapid inertial power ramp,frequency transients,BESS inertial response,synchronous machine measurements,inertia devices,RoCoF,synchronous machines monitoring,frequency 6.4 kHz