谷歌浏览器插件
订阅小程序
在清言上使用

Diagnosis of transformers based on vibration data

2019 IEEE 20th International Conference on Dielectric Liquids (ICDL)(2019)

引用 5|浏览11
暂无评分
摘要
Transformers with loose or deformed windings can fail during an external short circuit with loss of service and heavy maintenance costs. The transformers' tank vibration technique potentially offers a decisive solution for an on line continuous assessment of the integrity of structural elements in transformers. In this paper, the influence of sensor location on tank vibration measurements is addressed by means of Support Vector Machine (SVM) algorithms. Laboratory tests have been carried out in different points of the tank, on a typical oil filled power transformer under two extreme conditions, tight and loose windings. Preliminary results of SVM analysis of tank vibration spectra showed that it is possible to correctly identify winding looseness during repetitive sensor installation.
更多
查看译文
关键词
oil filled Transformers,Loose winding monitoring,Vibration measurement,Fault diagnosis,Support Vector Machine (SVM)
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要