Experimental study on vertical rigid and flexible polyurethane fire suppression using water spray

JOURNAL OF THERMOPLASTIC COMPOSITE MATERIALS(2022)

引用 1|浏览18
暂无评分
摘要
A series of vertical fire suppression experiments on rigid polyurethane (RPU) and flexible polyurethane (FPU) with/without water spray were conducted in a standard chamber. A new video processing method was developed to determine the pyrolysis front position of wind-aided flame. Averaged flame height, carbon monoxide/hydrogen cyanide concentration, view factors, and extinguishing time were determined with operating pressure varying from 0.15 MPa to 0.4 MPa. The experimental study showed that water spray would suppress RPU/FPU fire mainly by fuel surface cooling. Furthermore, the perfect water spray pressure for RPU/FPU fire suppression was 0.3 MPa and the corresponding water application rate was 0.7511 mg/(cm(2)center dot s).
更多
查看译文
关键词
Rigid polyurethane, flexible polyurethane, vertical fire suppression, water spray, extinguishing