谷歌浏览器插件
订阅小程序
在清言上使用

Mis-estimation of the System State ( Voltage Phasors ) by altering Voltage / Current Measurements Compromise

semanticscholar(2016)

引用 0|浏览3
暂无评分
摘要
Smart-grid applications based on synchrophasor measurements have recently been shown to be vulnerable to timing attacks. A fundamental question is whether timing attacks could remain undetected by bad-data detection algorithms used in conjunction with state-of-the-art situational-awareness state estimators. In this paper, we analyze the detectability of timing attacks on linear state-estimation. We show that it is possible to forge delay attacks that are undetectable. We give a closed form for an undetectable attack; it imposes two phase offsets to two or more synchrophasor-based measurement units that can be translated to synchrophasors’ time delays. We also propose different methods for combining two-delays attacks to produce a larger impact. We simulate the attacks on a benchmark powertransmission grid, we show that they are successful and can lead to physical grid damage. To prove undetectability, we use classic bad-data detection techniques such as the largest normalized residual and the χ-test.
更多
查看译文
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要