Efficient And Comprehensive Evaluation Method Of Temporary Overvoltage In Distribution Systems With Inverter-Based Distributed Generations

SUSTAINABILITY(2021)

引用 2|浏览0
暂无评分
摘要
In general, a temporary overvoltage (TOV) on the healthy phases occurs because of the neutral-shift phenomenon during a single line-to-ground (SLG) fault. The TOV can destroy the insulation of electric devices and cause damage to other equipment and customer loads in just a few cycles. In practice, the TOV can be affected by numerous factors: the sequence reactance ratio of the interconnection transformer, the ratio of load to DG, and the distance to the fault. More importantly, inverter-based distributed generations (DGs) have different influences on the TOV from traditional synchronous-machine-based DGs. In this sense, this work performed an efficient and comprehensive investigation on the effect of these various parameter types and their extensive variations, based on steady-state analysis with sequence equivalent circuits and three-dimensional representations. The proposed methodology can facilitate judging the impact of multi-parameter conditions on the TOV readily and comparing the fault characteristics of synchronous-machine-based and inverter-based DGs. Finally, the results can be used for future studies on TOV mitigation techniques.
更多
查看译文
关键词
3D graph, distributed generation, effective grounding, inverter-based DG, single line-to-ground fault, temporary overvoltage (TOV)