Net-Zero Water (NZW) Reuse Desiccant Assisted Evaporative Cooling System for Data Centers

David Okposio,A. G. Agwu Nnanna, Harvey Abramowitz

Volume 8: Heat Transfer and Thermal Engineering(2019)

引用 0|浏览0
暂无评分
摘要
Abstract The cooling effect of evaporative cooling systems is well documented in literature. Evaporative cooling however introduces humidity into the cooled space, which is unsuitable for data centers. Desiccants (liquid, solid or composites) adsorb moisture from the cooled air to control humidity and is regenerated using waste heat from the data center. This work is an experimental and theoretical investigation of the use of desiccant assisted evaporative cooling for data center cooling according to ASHRAE thermal guideline TC 9.9 . The thickness of the cooling pads is varied with specific surface area, velocity of air through the pad measured, the product of the air velocity and surface area yields the volumetric flowrate of the air, the water flow rate varied as well. The configuration is such that the rotary desiccant wheel (impregnated with silica gel) comes after the evaporative cooler. A novel water recovery system using the Peltier effect is proposed to recover moisture from the return air stream thereby optimizing the water consumption of evaporative cooling technology and providing suitable air quality for data center cooling.