Testing Mixed Application of Analog and Process Bus Environment in Transformer Differential Protection

CIRED 2021 - The 26th International Conference and Exhibition on Electricity Distribution(2021)

引用 0|浏览1
暂无评分
摘要
In a digital substation automation system introduced by IEC61850 standard, various technologies may co-exist with multiple vendors and combinations of analog and digital measurement signals. In this paper, a case study of a distribution power substation has been developed. The objective is to test the transformer differential protection during internal and external faults, inrush, sympathetic inrush, and over-excitation while combining both conventional and multi-vendor process bus technologies. The effect of communication network imperfection such as constant and random delay on the packet are emulated and the protection relay response is analyzed. The preliminary test indicates that mixed applications of conventional and process bus is fully functional in case of same vendor combination of merging unit and relay protection. The multi-vendor combination does not affect relay operation during faults, but protection relay shows incorrect blocking signal in case of over-excitation. Network imperfections and delays of more than 2 ms blocks the tripping signal during internal faults. Simulation and experimental results were carried-out for the MUs and differential protection in a multi-vendor environment.
更多
查看译文
关键词
transformer differential protection,digital substation automation system,IEC61850 standard,digital measurement signals,distribution power substation,internal faults,external faults,multivendor process bus technologies,communication network imperfection,protection relay response,tripping signal,analog measurement signals
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要