Protection performance assesment with grid forming converter acting as a reference genrator during black start

16th International Conference on Developments in Power System Protection (DPSP 2022)(2022)

引用 0|浏览4
暂无评分
摘要
The studies presented in this paper aim to assess the operation of existing protective schemes (i.e. overcurrent protection) within UK networks, considering black-start scenario initiated from converter-based distributed energy sources. The primary objective is to investigate whether it is realistically feasible for a converter-based battery storage unit, to replace a synchronous generator in black-start scenarios, and deliver the same benefits accounting for adequate fault levels and reliable protection operation. The case studies include transmission and distribution level (11kV up to 400kV) fault level calculations and assessment of the protection performance under balanced/unbalanced faults considering existing settings proposed for such black-start conditions. Furthermore, the utilization of a voltage-controlled overcurrent protection scheme is investigated as a potential protection solution, to address the reduced fault levels resulting from the converter-based source. The results and observations aim to build a solid foundation for the design of protection schemes during black-start scenarios within distribution systems.
更多
查看译文
关键词
voltage 11.0 kV,voltage 400.0 kV,protection performance assesment,converter acting,black start,protective schemes,black-start scenario,converter-based battery storage unit,adequate fault levels,reliable protection operation,distribution level,black-start conditions,voltage-controlled overcurrent protection scheme,potential protection solution,reduced fault levels,converter-based source,protection schemes
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要