Coordinated DC Interruption Method Based on Magnetic Coupling Current-Limiting and Dissipation

IEEE Transactions on Power Electronics(2023)

引用 4|浏览11
暂无评分
摘要
A flexible dc grid is important for supporting large-scale new energy integrations. To ensure the stable operation of the dc grid, a dc circuit breaker (DCCB) is needed for fault isolation. At present, the cost of DCCBs is high, and the breaking capacity is limited. This limitation can be effectively solved through the coordination of fault current limiters (FCLs) and DCCBs. In this article, a coordinated interruption topology of an magnetic coupling FCL (MCFCL) and hybrid DCCB is proposed. A coordinated interruption strategy based on magnetic coupling current-limiting and energy dissipation is proposed to improve the dynamic performance of the FCL and reduce the energy dissipation and breaking time of the DCCB. A two-stage mathematical model of coordinated interruption is established, and its control principle is analyzed. Furthermore, the influence of the inductance and resistance of the MCFCL secondary side, coupling coefficient and rated voltage of the arrester on the coordinated interrupting process is researched. On this basis, parameter optimization and economic analysis are carried out. Finally, a scaled test for the coordinated interruption of the DCCB and MCFCL was carried out, which verifies the feasibility of the coordinated interruption strategy based on magnetic coupling current-limiting and energy dissipation.
更多
查看译文
关键词
DC circuit breakers (DCCBs),DC power trans- mission,electromagnetic coupling,fault current limiters (FCLs)