A Fast Calculation of Partially Corroded, Grounding-Resistive Electrode Electrical Parameters

APPLIED SCIENCES-BASEL(2022)

引用 0|浏览4
暂无评分
摘要
Featured Application The proposed model can be applied to the assessment of the electrical parameters of non-perfect conducting grounding electrodes that are partially affected by corrosion. The calculation of the grounding resistance of electrodes built with partially oxidized non-perfect conductors is addressed in this paper. A model based on circuit analysis to account for internal resistance is used, while the oxidation or partial coating of the conductor surface is modeled using the concept of the equivalent radius of the coated electrode. From the proposed model, the values of the electrical parameters of the grounding electrodes, such as the grounding resistance and the step and touch potentials, are calculated for real electrodes affected by coating or corrosion and compared with those values under ideal conditions. The results show significant differences in certain configurations that may compromise the safety margins established by current regulations.
更多
查看译文
关键词
non-perfect conducting grounding electrodes, coated electrode equivalent radius, partially corroded electrode