Effect of horizontal connection pipes on operation of borehole heat exchangers under different climatic conditions

GEOTHERMICS(2023)

引用 0|浏览4
暂无评分
摘要
We investigate the effect of horizontal connection pipes in shallow geothermal systems attached to a borehole field for the 25 most representative climate zones across the World. For this we use a comparable 30 m connection pipe buried at 1 m depth connected to a 100 m deep borehole heat exchanger (BHE) as the unit representation of the whole system for all locations. The system is considered monovalent with weather dependent loads derived from local air temperatures. The connection pipes and BHE are modeled using thermal resistances and response functions. In the investigated reference scenario, the consideration of the connection pipes leads to an average reduction in BHE load of 34% in tropical climates, 19% in temperate climates, 11% in arid and 4% in continental climates, leading to a significant drilling cost reduction. Exceptions were the cities of Moscow and Heihe both located in continental climates and under severely colder conditions, where the BHE load increased by 13% and 72% due to consideration of the horizontal connection pipes, leading to a reduced efficiency or the need for additional drilling only for these cases.
更多
查看译文
关键词
Borehole heat exchanger, Horizontal connection pipe, Header pipe, Heat loss, Heat gain, Climate, Cost reduction