Comparison of Fire Suppression Techniques on Lithium-Ion Battery Pack Fires

MINING METALLURGY & EXPLORATION(2023)

引用 0|浏览6
暂无评分
摘要
Lithium-ion battery pack fires pose great hazards to the safety and health of miners. A detailed experimental study has been conducted at the National Institute for Occupational Safety and Health (NIOSH) Pittsburgh Mining Research Division (PMRD) to investigate the effectiveness of different fire suppression systems on Li-ion battery pack fire extinguishment. Tests were conducted in a well-ventilated container. Two sizes of battery packs (12 V, 24 V) were heated by heater strips to trigger thermal runaway and fire. Water mist with different flow rates, ABC powder, type D dry chemical, and water mist with F500 additives were used as the fire suppression agents. Multiple thermocouples were installed on the battery packs to measure the temperature evolution during the tests. The results indicated that the water mist with F500 additives is the most effective suppressant among the agents tested. Dry chemicals, however, do quench the fire for a moment, but cannot prevent re-ignition of the battery since they do not provide enough cooling. The findings of this paper can be used to develop safer battery fire suppression techniques in mining environments.
更多
查看译文
关键词
fire suppression techniques,lithium-ion
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要