谷歌浏览器插件
订阅小程序
在清言上使用

Non-contact On-Line Overvoltage Measurement System for Overhead Transmission Line

2022 IEEE International Conference on High Voltage Engineering and Applications (ICHVE)(2022)

引用 0|浏览4
暂无评分
摘要
Overhead transmission lines are easily disturbed by lightning overvoltages, which endangers the insulation performance of transmission lines. The overhead transmission line overvoltage measurement system based on the voltage divider has good accuracy. However, the long-term access of the voltage divider to the gird is easy to bring potential dangers to the power system. This paper proposed a non-contact, accurate, and real-time overvoltage measurement system to monitor the lightning overvoltages of the overhead transmission lines. The high voltage arm capacitor is composed of the overhead transmission line and the measurement electrode. The measurement electrode and the low voltage arm capacitors were integrated on a PCB board. The calibration and lightning overvoltage measurement experiment proved that the system had a broad bandwidth and excellent measurement accuracy. The non-contact overvoltage measurement system provided a new idea for overvoltage detection of the overhead transmission lines.
更多
查看译文
关键词
calibration,lightning overvoltage measurement experiment,lightning overvoltages,measurement electrode,noncontact overvoltage measurement system,on-line overvoltage measurement system,overhead transmission line,real-time overvoltage measurement system,transmission lines