Simulation study on abnormal discharge in insulator of fiber optical current transformer

2022 IEEE International Conference on High Voltage Engineering and Applications (ICHVE)(2022)

引用 0|浏览3
暂无评分
摘要
When the multi-terminal hybrid DC transmission project is put into operation, it is found that the failure rate of FOCT increases. In this paper, the finite element simulation model of FOCT is built. The influence of different fiber sheath materials and gel conductivity parameters on the electric field distribution characteristics is studied by simulation. The causes of abnormal discharge are summarized, and the improvement measures and suggestions are given. The results show that The internal discharge near the fittings is mainly due to the introduction of potential in the shielding area and the mismatch of gel and fiber material parameters. Measures such as selecting appropriate conductivity materials in multilayer media and appropriately increasing the length of insulators are proposed. The research results can provide reference and support for fault analysis and structural improvement