Dynamic Short Circuit Ratio for Stability Assessment of Grid Connected VSC-HVDC Systems Considering the Impact of Time-Varying Phase Shift

IEEE TRANSACTIONS ON POWER SYSTEMS(2024)

引用 0|浏览9
暂无评分
摘要
As more renewable resources are integrated into the receiving-end AC grid through VSC-HVDC, the grid connected VSC-HVDC system is facing a critical dynamic stability issue involving multiple-frequency oscillatory behaviors, which mainly stems from the low-system-strength and the time-varying phase shift. This paper proposes a general stability analysis method to measure the dynamic stability of grid connected VSC-HVDC system from the point of view of input to state stability (ISS). A nonlinear time-varying discrete-time state space model ((NTDSM)-M-2) of the grid connected VSC-HVDC system is built considering the impact of the time-varying phase shift. Then, the (NTDSM)-M-2 is decomposed into several interconnected subsystems. The general asymptotic gain matrix (GAGM), whose elements are derived from the proposed dissipative-form sum-type inequalities (DSIs), is constructed to quantify the interactions between multiple subsystems. Finally, a general dynamic stability analysis index, called dynamic short circuit ratio (DSCR), is proposed to effectively explain the critical dynamic instability point of the grid connected VSC-HVDC system, based on the spectral radius property of the GAGM. Moreover, the real-time simulations and multiple comparative studies are implemented in this paper to verify the effectiveness of the proposed (NTDSM)-M-2 and stability analysis method by using RT-LAB platform.
更多
查看译文
关键词
Power system stability,Circuit stability,Asymptotic stability,Stability criteria,Time-varying systems,Integrated circuit modeling,Analytical models,Short circuit ratio,dynamic stability,input to state stability,grid connected VSC-HVDC system
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要