Method to delay frost formation under high relative humidity by choosing proper heat exchange temperature difference and air velocity

Zongsheng Zhu, Wei Dou,Baomin Dai, Xiaofang Shan,Jiang Shen

SSRN Electronic Journal(2023)

引用 5|浏览0
暂无评分
摘要
To delay frost formation and maintain high heat transfer capacity of an evaporator, a closed-loop wind tunnel was designed and constructed to investigate the effect of heat exchange temperature difference (ΔT) and air velocity on frost formation characteristics, refrigerating capacity and water removal of air. The closed-loop wind tunnel provided flowing air at temperature of −18 °C, relative humidity of 85% and velocity from 2 to 5 m/s. During experiment, three obvious stages of frost thickness were found when air initial velocity was 3–5 m/s. With ΔT changing from 7 to 3 °C, the water removal of air through the evaporator decreased by 3–5 times and the high efficient operation time ratio (HETR) increased by 2–3 times. Meanwhile, the average frost mass reduced by about half at any fixed air velocity. When ΔT was 7 °C and air velocity was 2 m/s, the average refrigerating capacity was almost equal to that when ΔT was 3 °C and air velocity was 5 m/s. The combined results showed that smaller ΔT and larger air velocity was useful to forbid frost formation, and to maintain stable high refrigerating capacity and relative humidity.
更多
查看译文
关键词
frost formation,high relative humidity,temperature
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要