Effect of selected parameters on the electrical strength of a high-voltage vacuum insulation system

ARCHIVES OF ELECTRICAL ENGINEERING(2023)

引用 0|浏览4
暂无评分
摘要
The article presents the results of laboratory measurements of ???????????? breakdown voltages in a high-voltage vacuum insulating system for different pressures, contact gaps, type of electrode contacts and type of residual gas inside the discharge chamber. First of all, the electrical strength of the discharge chamber with a contact system terminated with contact pads made of W70Cu30 and Cu75Cr25 material was compared for selected values of contact gaps. It was found that below a pressure of ?????? = 3.0 x 10-1 Pa the electrical strength reaches an approximately constant value for each of the set contact gaps ??????. Analytical relationships were determined to calculate this value for each of the contact pads used. Above a pressure of ?????? = 3.0 x 10-1 Pa, the measured values of ???????????? breakdown voltages decrease sharply. The values of breakdown voltages in the discharge chamber with residual gases in the form of air, argon, neon and helium were also determined for selected values of contact gaps ??????. Depending on the residual gases used, significant differences were noted in the values of pressure ?????? at which the loss of insulating properties in the discharge chamber occurred. These values were 3.3 x 10-1 Pa for argon, 4.1 x 10-1 Pa for air, 6.4 x 10-1 Pa for neon, and 2.55 x 100 Pa for helium, respectively.
更多
查看译文
关键词
electrical breakdown, electrical contacts, electrical strength, switchgear, vac-uum insulation