Audible Noise and Corona Discharge From Water Droplets on Superhydrophobic HVAC Conductors

IEEE TRANSACTIONS ON POWER DELIVERY(2023)

引用 0|浏览1
暂无评分
摘要
Audible noise from transmission lines is mainly generated by corona discharge from defects and water droplets on the conductors' surface. Applying a superhydrophobic coating to the conductors can reduce corona discharge, thereby reducing the level of audible noise produced. In this article, corona discharge and noise measurements from an untreated conductor and a conductor coated with superhydrophobic coatings were carried out in AC electric fields and continuous water spray. The coated conductors show higher partial discharge inception voltages (PDIV) than uncoated ones. PD magnitude and PD per cycle of the coated conductors are lower compared with uncoated conductors, especially at electric fields above 14 kV/cm. A linear correlation between overall sound pressure and total PD magnitude is established. The behavior of corona discharges from single droplets with various sizes and positions and associated droplet vibration were investigated and the local electric field enhancement was analyzed by finite element analysis to examine the influence of droplet size and position on electric field distribution. Superhydrophobic coatings result in reduced PD magnitude and number and therefore reduce audible noise generated. This is attributed to small sessile droplets forming rather than large pendant droplets.
更多
查看译文
关键词
Conductors,Corona,Surface discharges,Coatings,Partial discharges,Acoustic noise,Discharges (electric),Audible noise,corona discharge,overhead line conductors,superhydrophobic coatings,water droplets
AI 理解论文