Large eddy simulations fire modeling of JIS A 1310 fa?ade calibration test with respect to sidewall

FIRE AND MATERIALS(2024)

引用 0|浏览2
暂无评分
摘要
The full-scale facade standard test is widely employed as a comprehensive method to assess the facade fire spread. Within this approach, the calibration test without combustible facade decouples the intricate interaction between gas-phase combustion and material pyrolysis, which simplifies diagnostics and provides an ideal scenario for model validation. This paper presents large eddy simulations (LES) accompanied by comparisons of calibration tests in accordance with JIS A 1310. The calibration tests were conducted to obtain the flame morphologies, gas-phase temperature, and heat flux of over-ventilated facade fires, and the LES modeling is complemented by the modified eddy dissipation model for combustion, the one-equation model for the sub-grid scale turbulence, and the discrete ordinate method with the gray mean absorption-emission approach for thermal radiation. The accuracy of LES data is discussed by comparing with measurements, and the mesh resolution is optimized as 2.5 cm for achieving mesh independency with good qualitative agreement. Furthermore, simulations are conducted to investigate the impact of sidewall distances on facade flame spread. The results highlight that the enhancement of sidewall in facade flame spread occurs under external heat release rate, and the 0.2 m sidewall distance for the designated JIS test is identified as a critical threshold increasing facade thermal load.
更多
查看译文
关键词
calibration test,facade fire,JIS A 1310,large eddy simulation (LES),sidewall distance