Taking the 70-meter-high lattice-type steel pipe free-standing lightning rod in the Ganzi 1 000 kV substation as an example,this paper conducts a comparative computational analysis based on the Technical Specification for Architectural Structure Design of Substations(DL/T 5457-2012)and the Load Code for the Design of Building Structures(GB 50009-2012).Differences in key parameters such as wind vibration coefficients,wind pressure height variation coefficients,de-formation,and structural internal forces under the two codes are systematically compared.Design recommendations are provided to offer references for practical engineering projects.
电网公司受到前期建设投资不均衡、技术改造不精准等因素影响,设备资产将在未来集中老化.现有的技改投资方案未充分考虑老旧设备更替的需求,形成了"资产墙"风险.通过采用生存概率模型优化"资产墙"预测方法,建立考虑了"资产墙"风险的电网投资策略和技改投资需求模型.通过对"十四五"期间某省级电网公司技改方案测算验证,使用本方法能够准确定位未来技改投资需求高峰期,实现投资风险的精准预测,有效辅助电网技改投资规划.
某热电厂因无备用热源等原因,近年来无法满足日益增长的供热负荷需求,且供热安全性和可靠性亟需增强;同时全厂机组的综合调峰能力不足,无法获得更深度调峰的收益.针对这些问题,提出了对 2 号机组实施低压缸零出力供热改造,增设 1 台 40 MW高压电极热水锅炉和 1 台 35 MW高压电极蒸汽锅炉,并配套 500 m³常压蓄热水罐的技术改造方案,以满足备用热源、调峰、启动锅炉改造需求.通过对改造方案供热能力和调峰能力分析可知,本方案改造后可使全厂发电标准煤耗下降21.3%;供热标准煤耗下降0.56%.电锅炉参与调峰后,所获得的年度综合收益为 1 712.88 万元;切缸改造后获得的收益约为 2 634 万元;项目整体总收益为 4 346.88 万元.可获得明显的经济效益.
母线导体的可靠连接是保证GIS中电能正常传输的前提,合理的导体结构设计对母线安全运行至关重要.介绍了一起 110 kV三相共箱式GIS母线在运行过程中出现电压波动、异音和气体组分超标的异常运行事件,现场X射线检测发现母线导体存在漏装限位螺钉以及同一导体两侧限位螺钉被同时挤压变形的现象,进一步通过理论计算和推理分析得出导体与两侧触头座内限位螺钉间的设计活动裕度不满足要求.针对此现象,结合实际运行条件提出了安全、合理、经济的结构改进措施,并开展了同结构两条母线整体改造工作,改造效果较为显著,为后续此类问题的发现和解决提供了思路.
水库中长期发电优化需要考虑来水情况、工程安全及防洪需求等因素,是一个多变量、多约束的复杂非线性优化问题.以百色水库为研究对象,在考虑各类安全约束条件下,以水库年发电量最大为目标,建立年发电优化模型,根据水库往年的水文数据,采用基于自适应权重的改进粒子群优化算法对模型进行求解.计算结果表明:采用所建立模型和算法对水库运行进行优化后年发电量有所提升,对指导水库安全经济运行有较积极的指导意义.