Current transformers (CTs) are precision devices that scale high currents down to values that can be easily handled by measurement equipment. To support CT applications in revenue metering, a comparison on AC current transformer calibration systems was performed among 15 European national metrology institutes using a precision CT as the travelling device. The first comparison results for the transformation ratios (4, 5, 6, 8, 10) kA/5 A of the travelling CT at nominal burden of 5 VA and 15 VA indicate good agreement between the participating laboratories. The main differences are found for phase displacement, at least partly caused by the instability of the traveling standard.