为提高1 000 MW超超临界二次再热锅炉蒸汽吹管系数,改善管道吹扫质量,对某电厂3号锅炉吹管系数偏低原因进行了分析,认为临吹门前的管路阻力过大导致了过热器吹管系数偏低,指出了超高压主汽门、临吹门、支管弯头等三处阻力增大点,并利用了临吹门与主蒸汽管通流面积比来评估临吹门的通畅性.基于3号锅炉的研究结论,对4号锅炉临吹系统进行了针对性的阻力优化,采用临时管将超高压主汽门旁路,同时临吹门改用双阀-支管布置方式.采用上述改进措施后,在过热器单吹阶段,4号锅炉较3号锅炉最大吹管压降比值提高21.6%,过热器出口蒸汽压力则降低23.1%;在过热器与再热器串联吹扫阶段,4号锅炉过热器、一次再热器、二次再热器最大吹管压降比值,较3号锅炉分别提高45.8%、68.7%、64.1%,过热器出口蒸汽压力则由9.3 MPa降低至8.5 MPa,吹管全程过热器压降比值稳定维持在1.40以上,蒸汽吹扫质量与临时吹管系统的安全性均得到可靠保障,相关经验可供后续同类机组参考.
为降低机组汽轮机(简称大机)抽汽的过热度,减少换热过程的不可逆损失,提出并应用一种由变流器主控带小发电机的抽汽背压式给水泵汽轮机(BEST)系统,该汽轮机(简称小机)在驱动锅炉给水泵的同时,其多余功率由配套的小发电机消纳转换,产生的电能供厂内设备使用,从而有效降低厂用电率.实际应用中发现,BEST小机剩余功率过大,触发"电负荷超限"保护动作,小机进汽调节阀关小,带来锅炉给水流量的大幅波动,机组因"给水流量低"保护动作而跳闸.分析运行曲线,认为小机背压异常偏低,蒸汽焓降过大,导致BEST小机剩余功率超过设计值,引起小发电机"负荷超限".通过优化调整抽汽回热系统投运方案,逐步建立起小机的合理背压,使得小机在各转速下的剩余功率均处于正常范围,BEST给水泵系统电负荷超限问题获得妥善解决,有力保证了机组后续试运工作.相关调试调整经验可供同类型机组参考.
为分析1 000 MW超超临界机组锅炉高温再热器爆管原因,对泄漏管段进行了现场取样,并开展了外观检查、硬度检测、室温拉伸检测以及金相分析等多项检测.结果表明:高温再热器管材各项性能指标符合标准要求,爆管原因为通流不畅引发的材料局部过热.为彻底清除受热面系统内可能残留的其他异物,排除再次爆管隐患,针对已连接完善的机炉蒸汽管道系统,依靠汽轮机高低压旁路系统,提出并应用了"二次吹管"技术方案,在凝泵滤网处顺利捕获大量杂质,二次吹管方案实际应用效果良好.相关经验可为同类机组提供参考.
在抽汽背压式汽轮机(backpressure extraction steamturbine,BEST)构成的双机回热系统中增设电机变流器组,可使BEST启动更具有灵活性.对该系统的运行及控制方式进行了介绍,并在机组试运过程中,在不同运行工况下进行了一系列系统的试验.结果表明:变流器对BEST转速的控制精准度较高,且变流器电动工况与发电工况可平稳切换;此外,事故工况下,变流器与小汽轮机电液控制系统(micro electro-hydraulic control system,MEH)之间的控制切换具有迅速、扰动小的特点,保障了机组运行的稳定安全.以上试验验证了变流器在BEST驱动给水泵系统中应用的实际可控性、安全性和稳定可靠性.最后,通过经济性计算,投入变流器后机组在热耗率验收工况下满负荷运行时可节约标准煤约2.1 g/(kW·h),具有一定的经济效益.
本文针对电厂断路器闪络导致主变压器损坏的实例,分析在磁场断路器断开瞬间,发电机励磁回路的暂态过电压对发电机端电压的影响,以及和断口闪络保护和失灵保护的总时限与变压器动稳定能力之间的配合关系,认为目前标准规定的断路器闪络保护与失灵保护配合不能有效地保护主变压器.根据分析结果,提出对现有装置缩短断路器闪络与失灵保护时限;或通过改变断路器闪络保护的出口方式,使其直接动作于故障断路器的所有相邻的断路器或所在母线所有断路器.
为适应内蒙古地区干旱缺水的环境特点,降低火电机组的水耗,针对660 MW超超临界褐煤锅炉的技术特性,提出并应用了一套回收锅炉烟气中水分并加以利用的节水装置.该装置通过在脱硫塔出口烟道内加装冷却器,降低了烟气温度,使得烟气中的水蒸气受冷凝结,并汇集成有利用价值的液态水.实际运行结果表明,该烟气取水装置具有节水效果显著、出力调整灵活等优势.同时,为充分利用该回收水,对相关设备进行优化改造,增加脱硫吸收塔补给水与湿式电除尘器集尘板冲洗水两路用户,进而保证了设备的长期可靠运行,并取得了节水与降尘双重效益.相关设备的改造经验可供后续同类设备的优化改造提供参考.
为提高能源利用效率,降低火电机组供电煤耗,提出一种可同步回收锅炉烟气和引风机小汽轮机(小机)蒸汽余热的集成式一体化节能装置.该系统以热媒水作为能量传递转换的载体,通过设置独立的小机凝汽器与低温省煤器,协同回收汽轮机排汽及锅炉排烟2种不同形式的余热,升温后的热媒水进入暖风器,将热量统一利用,加热入炉一次风、二次风.最终,借助热媒水的强制循环流动,实现了蒸汽-烟气余热的协同回收联合利用,机组运行经济性得到进一步提升.实际运行结果表明,该余热联合利用系统具有投用灵活、季节适应性强、节能效果显著等优势,应用后机组发电标煤耗降低3.948 g/(kW·h),脱硫系统减少耗水量20t/h,单台机组年收益增加约360万元.本文相关经验可供后续同类机组参考.
目前国内光伏电站使用的主流组件为单晶PERC(passivated emitter rear cell)组件,PERC电池结构特点决定其对硅片表面状态非常敏感,背面钝化膜与硅片间出现任何异常或污染,均会导致PERC电池EL下出现黑斑或黑点.设计对比试验,通过量子效率测试以及LBIC分析,研究黑斑对于电池片性能的影响,再用多个电池片封装成组件,通过LID试验分析PERC电池EL黑斑对于组件性能的影响,结果表明黑斑对于电池片性能的影响较小,通过CTM分析在同样投入成本的情况下,组件制造厂家可通过减少EL黑斑组件来增加自己的产能和利润,而PERC电池EL黑斑对于光伏组件光致衰减的影响很大,而且不可逆,这说明EL黑斑主要是杂质金属污染所致,这也更深入的解释了EL黑斑形成的原因,对于工程设备的质量把控和监造提供理论支撑.
二次再热技术以其较高的经济性正得到越来越广泛的应用,我国目前尚无二次再热机组工程投产的实例,相关启动运行经验较为缺乏.以国内第1台660MW等级超超临界二次再热锅炉为研究对象,介绍了机组锅炉的主要特点,并从冷态通风试验、新型吹管工艺、低负荷稳燃、燃烧初调整等方面阐述了二次再热锅炉关键调试技术.针对机组试运行期间出现的燃烧器、风机、控制逻辑等问题给出了解决办法.经过调整优化,机组运行稳定、性能可靠,各项参数均达到了投产要求.
选用大疆inspire 1无人机作为飞行平台,搭载FLRE Vue机载热像仪机芯,并选用三星的S3C6410处理器作为嵌入式终端,成功实现了自动化检测热斑效应;通过开发软件对出现热斑效应的组件进行分析处理,得出了具体的热斑检测报告.通过无人机检测光伏组件热斑,大幅提高了电站红外热斑检测效率.
To explore suitable pipe-blowing methods for ultra supercritical double-reheat units, a decompression combined pipe-blowing method was proposed and put into practice on the domestic first double-reheat boiler. This new method is a combination of "one section pipe-blowing" method's structure and "two-section pipe-blowing" method's operating characteristics. The superheater, primary reheater, secondary reheater and its associated pipelines were connected in series in one time. The whole system is divided into three parts, and each part is purged and targeted separately. For the problem that the steam purge coefficient does not satisfy the standard, field test and theoretical analysis were carried out. Some measures, such as increasing the separator outlet steam pressure, opening multiple valves simultaneously, were taken into practice to eliminate the blocking flow effect and guarantee the purging quality. The final target plate tests results show that, the depression combined pipe-blowing method completed the purging of double-reheat boiler heating surfaces with high quality. This method can provide practical reference for other similar units.
The reheat steam temperature of China's firstly built double-reheat boiler is sharply lower than the design value. To solve this problem, the quality of coal as fired and the heat absorption capacity of the boiler heating surface was analyzed. Moreover, the flue gas recirculation thermal control scheme was improved. On this basis, the comprehensive temperature improvement scheme was proposed, including optimizing the coal mill combination type, regulating the burner elevation angle, increasing the over fired air volume, improving the soot-blower's putting-in-service mode and adjusting the flue gas recirculation amount. Furthermore, the condition test to explore the effect of burner's swinging angle and flue gas recirculation fan speed on temperature of the first reheat and second reheat steam were carried out. After debugging optimization , the reheat steam temperature of the boiler can reach 610~620℃at high load and 590~590℃ at low and medium loads, which are similar with the design value, indicating the problem of low reheat steam temperature was solved well. The debugging experience has project reference value for subsequent similar units.
为研究钢结构小机间冷塔的阻力特性,以某电厂660 MW直接空冷机组小机间冷塔为研究对象,运用流体力学方程建立计算模型,借助ICEM-CFD及Meshing软件完成网格划分,利用Fluent软件计算了模型各处的流场特性,使用ANSYS软件计算了小机间冷塔各部位的阻力系数.结果表明,钢制空冷塔喉部区域负压最大,空气流速最大;X柱处局部阻力系数小于筒身处,折弯处的局部阻力系数最大;塔身各处局部阻力系数随雷诺数增大变化较小.
水是超超临界机组热力系统中重要的工作介质和冷却介质,锅炉补给水水质稳定合格对机组的安全运行十分重要.介绍了膜法+离子交换水处理技术(纤维过滤器/超滤/一级反渗透/一级除盐/混床)在某超超临界机组锅炉补给水处理系统中的应用情况,详细讨论了反渗透+离子交换水处理工艺特点、系统运行方式、控制参数和注意事项,比较了膜法+离子交换和全膜法工艺特点和经济性.运行结果表明,膜法+离子交换水处理系统出水水质稳定优良,符合超超临界机组锅炉补给水水质的要求.
1 事故现象 2010年8月4日,某发电厂4号主变压器A相套管发生爆炸,B、C相套管瓷套被炸坏,中性线出线套管外瓷套破损,发电机-变压器组差动保护、主变压器差动保护、主变压器中性点过流保护、主变压器重瓦斯保护动作,主变压器高压侧21C断路器、厂用高压变压器低压侧64A3A断路器、64B3A断路器跳闸.同时,现场发现中性点接地间隙击穿,变压器消防喷雾动作,主变压器压力释放装置动作.
所谓断路器失灵,就是当输电线路、变压器、母线或其他主设备发生短路时,保护装置动作并发出了跳闸指令,但故障设备的断路器拒绝动作或不能正确切除故障.系统发生故障之后,如果出现了断路器失灵而又没采取其他措施,将会造成严重的后果.它可能损坏主设备、引起火灾、扩大停电范围,严重时可能使电力系统瓦解.下面就一典型案例作分析.
<正>近年来,大容量机组多发生发电机转子接地故障,并且由于大容量机组励磁电流较大,发生发电机滑环环火事故的频次及故障损失也显著增大。当发电机接地故障发生时,机组不能及时跳闸是故障损失扩大的主要原因。本文分析了300 MW及以上容量发电机8次转子滑环烧损事故及3次其它类型转子接地故障,并调研了19家发电厂66台300MW及以上发电
<正>1事故概况某电厂4号机组主变压器型号为TFUM8754,额定容量435 MVA,额定电压242±2×2.5%kV/21kV,冷却方式为强迫油循环风冷。2010年8月4日
1 事故概况 某电厂4号机组主变压器型号为 TFUM8754,额定容量 435 MVA,额定电压242±2×2.5%kV/21kV,冷却方式为强迫油循环风冷.2010年8月4日20:54该主变压器A相套管发生爆炸,B相、C相套管瓷套被炸坏,中性点出线套管外瓷套破损,发变组差动保护、主变压器差动保护、主变压器中性点过流保护、主变压器重瓦斯保护动作,主变压器高压侧21C开关、厂用电高压变压器低压侧64A3A开关、6483A开关跳闸,现场发现中性点接地间隙击穿,变压器消防水喷雾动作,主变压器压力释放装置动作.
After merging the induced draft fan(IDF) of boiler with the booster air fan used for flue gas desulphurization of ultra-supercritical 1000 MW unit in one power plant,a small-turbine driven IDF has been adopted.The influence of turbine-driven IDF upon main operating indices of power plant has been analysed,results of analysis show that the adoptation of turbine driven large-capacity IDF can avoid impulse to the auxiliry electric system in start-up process of IDF,reducing substantially the consumption rate of service power.